Toshiba GR200 Series Instruction Manual page 646

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Output signal to BO
The SPOS01 function, in Figure 4.1-4, can issue a "Select success" signal at the output point
"SPOS01_FSL_BO_CSF" when the SPOS01 function determines that the "Select command Off
(Remote-OFF-Control)" signal is true. If the SPOS01 function determines that the "Remote-
OFF-Control" signal is not true, the SPOS01 function returns to the "Wait for a command"
stage.
Receiving "Selection command On" from the local-end
(iii)
Figure 4.1-5 outlines the reception of the selection command 'On' from the local-end.
Wait for a command
Selection logics
Select command On from remote-end
Select command Off from remote-end
Select command On from front panel
Signal reception
from the front panel
Select command Off from front panel
Select command On by the PLC
Select command Off by the PLC
Input signal generated at the local-end.
Figure 4.1-6 shows the select logic when a "Select command On (Local-ON-Control)" signal is
applied to the SPOS01 function. The signal is provided when an "On" key is pressed on the
IED front panel; the user is not required to map the signal from the IEC61850 communication.
Note that the user should set the scheme switch [SPOS01-CTRAHMI] to SBO when operation
from the IED front panel is required; we discuss how to set this in chapter
Control sub-menu
Selection logic
Figure 4.1-5 Outline of selection command 'On'
.
- 623 -
Failed
Select
Signal output
decision
Success
6F2S1914 (0.49)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
User interface:
GRL200 (Soft 033 & 037)