Operate logic for SBO/DIR modes
4.1.3
Once the operation of the select logic is completed, the operate logic start to control the device.
Receiving "operate command On" from the remote- end
(i)
Figure 4.1-19 depicts the reception of the operate command 'On' from the remote- end.
Wait for a command
Select logics
Select command On from remote-end
Select command Off from remote-end
Select command On from front panel
Select command Off from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Figure 4.1-19 Outline of operate command for 'On'
Mapping required for Input point
Figure 4.1-20 illustrates the operate logic when an "Operate command On (Remote-ON-
Control)" signal is applied to the SPOS01 function. The input-point "DEV01_CONTROL_REQ"
is used for the reception of the "Operate command On (Remote-On-Control)".
Wait for a next command
On control from remote-end
Operate logic
Signal reception in
IEC61850
Off control from remote-end
On control from front-panel
Off control from front-panel
On control by PLC function
Off control by PLC function
- 639 -
6F2S1914 (0.49)
Success
Operation
Signal output
decision
Do nothing
Failed
GRL200 (Soft 033 & 037)