Setting
2.29.9
FS (Function ID: 48B001)
Setting items
FS-EN
OCFS-EN
OCDFS-EN
EFFS-EN
OCMFS-EN
UVFS-EN
UVSFS-EN
DUVFS-EN
OC
OCFS
OCD
OCDFS
TOCDFS
EF
EFFS
UV
UVFS
UVS
UVSFS
DUV
DUVFS
TDUVFS
Range
Unit
1A rating
5A rating
Off / On
- Fail safe scheme switch
Off / On
- OCFS scheme switch
Off / On
- OCDFS scheme switch
Off / On
- EFFS scheme switch
Off / On-T / On-S
- OCMFS scheme switch
Off / On
- UVFS scheme switch
Off / On
- UVSFS scheme switch
Off / On
- DUVFS scheme switch
0.10 -
0.50 -
A OCFS relay operating value
50.00
250.00
0.05 -
0.25 -
A OCDFS relay operating value
0.20
1.00
0.00 - 300.00
s Extended time of OCDFS operating
0.10 -
0.50 -
A EFFS relay operating value
50.00
250.00
5.0 - 130.0
V UVFS relay operating value
5.0 - 130.0
V UVSFS relay operating value
1 - 20
V DUVFS relay operating value
0.00 - 300.00
s Extended time of DUVFS operating
- 365 -
6F2S1914 (0.49)
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
Off
Off
Off
Off
Off
Off
Off
1.00
5.00
0.10
0.50
10.10
0.20
1.00
46.0
80.0
5
10.10