Figure 2.6-2 Sending DIFL operation signals for remote terminals
†Note: The DIFL#2 element is only available in the [TERM_TOPOLOGY]=2Term-Dual.
Figure 2.6-3 exemplifies the IEEE C37.94 frame format for sending the signals "DIFL-
A,-B, and -C"; the COM5-4, COM5-5, and COM5-6 bits are assigned. The communication
application function (COMM_APPL) function provides transmitting feature. Thus, we should
map the signals "DIFL-A, DIFL-B, and DIFL-C" to PLC connection points "COM5-4_S, COM5-
5_S, COM5-6_S"†.
a. Sending frames for remote IE Ds in IEE E C37.94
N=1
Header
N=2
Header
N=3
Header
b. Connections for sending using PLC function†
From DIFL
8000101C20
DIFL-A
8100101C21
DIFL-B
8200101C22
DIFL-C
DIFL function
Figure 2.6-3 Mapping for sending signals using COM5 bits†
†Note: For more information, see
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].
Reception of DIFL-operation signal from the remote
Similarly, the DIFL function has reception points from the opposite-terminals. Figure
A
B
DIFL#1
C
A
B
DIFL#2
C
I 0
Ia
Ia2
Ia3
830216EBB3
COM5-4_S
840216EBB4
COM5-5_S
850216EBB5
COM5-6_S
COMM_ APPL function (Function ID: 4A9001)
8000101C20
≥1
8100101C21
≥1
8200101C22
≥1
V
Ib
Ib2
Ic2
Ib3
Ic3
COM5 (6bits)
1 2 3 4 5 6
Chapter Relay application: Communication application
- 61 -
6F2S1914 (0.49)
DIFL-A
DIFL-B
DIFL-C
Ic
CR C
I 0
CR C
COM5
CR C
CRC
CRC (8bits)
CRC (8bits)
GRL200 (Soft 033 & 037)
&
&
&
&
&
&
.

Advertisement