Figure 4.5-4 LN editing screen for SBO mode (for example)
Defining DIR mode
Figure 4.5-5 exemplifies the settings in LN "GGIO1301" when the DIR mode is required for
the TTIM01 function. In the DIR mode, the following three items should be selected using GR-
TIEMS:
Figure 4.5-5 LN editing screen for DIR mode (for example)
Mapping output data
(ii)
The user should group the TTIM01 signals with regard to GOOSE and REPORT; the user
should map them for IEC 61850 communication using GR-TIEMS.
Table 4.5-4 shows the mapping signals within the TTIM01 function required for IEC
61850 communication. Figure 4.5-6 shows how to map a signal.
✓
SBOw
✓
Oper
✓
Cancel
✓
Origin
✓
stSeld
✓
sboClass† (choice "operate-once")
✓
ctlmodel (choice "SBOes or SBOns")
†"sboClass" can be found by scrolling down.
✓
Oper
✓
origin
✓
ctlmodel (choice "DOes or DOns")