Receiving "Select command Off" from the local-end
(iv)
Figure 4.8-7 outlines the reception of the Select command 'Off ' from the local-end.
Wait for a command
Select stage
Select command On from the remote-end
Select command Off from the remote-end
Select command On from the local-end
Select command Off from the local-end
Signal reception
from the front panel
Select command On by the PLC function
Select command Off by the PLC function
Input signal generated at the local-end
Figure 4.8-8 shows the Select logic when a "Select command Off (Local-OFF-Control)" signal
is received is applied to the DPOS01 function. The signal is provided when the user presses
the "OFF" key on the IED front panel; the user is not required to map the signal from IEC61850
communication.
Output signal to BO
When the "select condition" signal is true, the DPOS01 function can issue a "Select success"
signal at the output-point "DPOS01_FSL_BO_FLG".
Note: The signal "DPOS01_FSL_BO_FLG" is the same as the signal shown in Figure
1
4.8-4. If the signal "Local-OFF-Control" is not true, the DPOS01 function returns
to the "Wait for a command" stage.
Select logic
decision
Figure 4.8-7 Outline of Select command 'Off'
- 848 -
Failed
Select
Signal output
Success
6F2S1914 (0.49)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
GRL200 (Soft 033 & 037)