Data ID
2.34.7
Signal monitoring point
ARC(Function ID: 4A6001)
Element ID
Name
8500001B6C
3PHASE FAULT
8000001B81
ARC IN-PROG
8000001BB3
ARC NO ACT
8000011B6C
ARC1 CLOSE COMMAND
8C00011B71
ARC1 CLOSE FAIL
8000011B72
ARC1 CLOSE SUCCESS
8400011B6E
ARC1 FT
8200011B61
ARC1 IN-PROG
8000011B60
ARC1 READY
8700011B70
ARC1 RESET
8000011B6B
ARC1 SHOT1
8100011B67
ARC1 SHOT2
8200011B68
ARC1 SHOT3
8300011B69
ARC1 SHOT4
8400011B6A
ARC1 SHOT5
8100011BC9
ARC1-S2 COND
8200011BCA
ARC1-S3 COND
8300011BCB
ARC1-S4 COND
8400011BCC
ARC1-S5 COND
8800011B74
ARC1-SUB_INIT
3000001B82
ARC1_AUTORECST
8000011BCF
ARC1_BLOCK
8000011B73
ARC1_INIT
8100011BB1
ARC1_MODE-FT
8500011BB5
ARC1_MODE-MPAR
8000011BB0
ARC1_MODE-OFF
8600011BB6
ARC1_MODE-ORG
8400011BB4
ARC1_MODE-S&T
8200011BB2
ARC1_MODE-SPAR
8300011BB3
ARC1_MODE-TPAR
8300011B66
ARC1_MPAR
8200011B65
ARC1_ORGAR
8000011B63
ARC1_SPAR
8100011B64
ARC1_TPAR
8100021B68
ARC2 CLOSE COMMAND
8C00021B6D
ARC2 CLOSE FAIL
8000021B6E
ARC2 CLOSE SUCCESS
8400021B6A
ARC2 FT
8200021B61
ARC2 IN-PROG
8000021B60
ARC2 READY
8700021B6C
ARC2 RESET
8100021B67
ARC2 SHOT
8900021B70
ARC2-SUB_INIT
Description
3 phase fault
No action for ARC
CB close command for ARC1
ARC1 fail
ARC1 success
Final trip for ARC1
ARC1 in progress
ARC1 ready
ARC1 reset when ARC no action or success
ARC1 shot1
ARC1 shot2
ARC1 shot3
ARC1 shot4
ARC1 shot5
ARC1 shot2 condition
ARC1 shot3 condition
ARC1 shot4 condition
ARC1 shot5 condition
ARC1 sub initiation
AutoRecSt signal in RREC of IEC61580 LN
ARC1 block signal
ARC1 initiation
Final trip mode for autoreclose 1
Multi-phase mode for autoreclose 1
Off mode for autoreclose 1
Original mode for autoreclose 1
Single and three-phase mode for autoreclose 1
Single-phase mode for autoreclose 1
Three-phase mode for autoreclose 1
For multi-phase ARC1 operation
For original ARC1 operation
For single-phase ARC1 operation
For three-phase ARC1 operation
CB close command for ARC2
ARC2 fail
ARC2 success
Final trip for ARC2
ARC2 in progress
ARC2 ready
ARC2 reset when ARC no action or success
ARC2 shot
ARC2 sub initiation
- 469 -