Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

DISCAR-OPT-A
&
DISCAR-OPT-B
&
DISCAR-OPT-C
&
&
From Z1G
Z1G-TRIP-A
Z1G-TRIP-B
Z1G-TRIP-C
Z1S-OPT
From SOTF-OC
OCH-RETRIP
DISCAR-CS-A_BOP
DISCAR-CS-B_BOP
DISCAR-CS-C_BOP
DISCAR-CS-S_BOP
800000EB55 DISCAR_F.BLOCK
810000EB56 DISCAR_PERMIT
Dis-CAR
BOP
Protection for week infeed terminal
2.12.5
Both POP and UOP are provided with ECHO and WIKT; both are used for a line including
weak infeed terminals.
ECHO function
(i)
With regard to POP, if a terminal receives a trip permission signal when neither forward
overreaching element nor reverse looking element have operated, ECHO sends back the
received signal to the opposite terminal.
With regard to UOP, if a terminal receives a block signal when neither forward
overreaching element nor reverse looking element have operated, ECHO stops sending the
block signal to the opposite terminal.
When CB is open, ECHO sends back the trip permission signal or stops sending the trip
block signal. User can set the time from CB opened to ECHO enabled using setting
[TCARECCB].
The terminal on which the forward overreaching element has operated can issue a trip
signal speedy by using the signal by ECHO.
Once the forward overreaching element or reverse looking element have operated,
transmission of the echo signal is inhibited for 250 ms by delayed drop-off timer T1 even after
these elements are reset.
To prevent any spurious echo signal from looping round between the terminals in a
TSCT-Dis
t
0
≥1
1
&
t
0
≥1
1
&
t
0
≥1
1
&
t
0
≥1
1
&
0.00 to 1.00s
Figure 2.12-6 Sending circuit of BOP
- 195 -
8000001B78
INT.DISCAR-S-A
8100001B79
INT.DISCAR-S-B
8200001B7A
INT.DISCAR-S-C
8300001B7B
INT.DISCAR-S-S
≥1
8F00001B7C
≥1
&
&
1
6F2S1914 (0.49)
used for the
integral carrier communication
used for the
DISCAR-S
external carrier communication
GRL200 (Soft 033 & 037)