Toshiba GR200 Series Instruction Manual page 116

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

As shown above, the positive-sequence impedance is used when determining settings for
phase faults.
Single-phase-earth fault
(ii)
Figure 2.10-2 shows the power system in the event of a single-phase-earth fault. It is very
difficult to measure precisely the distance to the fault point for a single-phase-earth fault. This
is because the impedance of the zero-sequence circuit including the earth return is generally
different from the positive-sequence impedance. Therefore, the faulted phase voltage is not
simply proportional to the faulted phase current.
It is necessary to analyze the impedance seen by the relay in the event of a single-phase-
earth fault according to the method of symmetrical components. Figure 2.10-3 shows an
equivalent circuit for a single-phase-earth fault based on the method of symmetrical
components. If we define the positive-sequence, negative-sequence and zero-sequence voltages
as being V 1 F, V 2 F and V 0 F, then the voltage at the relaying point of each symmetrical circuit
will be given by the following equations based upon the assumption that the positive-sequence
��
��
��
=
1
��
��
Va
Ib
Vb
Ic
Vc
ZS
Figure 2.10-1 Phase-to-phase fault
Ia
Va
Ib
Vb
Ic
Vc
ZG
Figure 2.10-2 Single-phase-earth fault
- 93 -
− ��
��
− ��
��
Zm
Zs
VaF
6F2S1914 (0.49)
(2.10-6)
VF
VF
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents