Toshiba GR200 Series Instruction Manual page 780

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Table 4.3-19 shows the required mapping signals in SOFTSW1 function to the IEC 61850
communications. Figure 4.3-25 shows how to map a signal.
Object_reference
Ctrl/GGIO701$SPCSO$origin
Ctrl/GGIO701$SPCSO$origin
Ctrl/GGIO701$SPCSO
Ctrl/GGIO701$SPCSO
Ctrl/GGIO701$SPCSO
Ctrl/GGIO701$SPCSO
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.3-25 orCat attribute mapped into SPCSO object of GGIO701
Mapping input data
(iii)
The SOFTSW1 function can receive three commands "select, operate, and cancel. Thus, the
user should map the input-point "S4301 _CONTROL_REQ". Table 4.3-20 shows the input-point
"S4301_CONTROL_REQ" and the Object reference "Ctrl/GGIO701$SPCSO" ; the user should map
the Object reference having attributes CO and CF in FC† to the input-point . Figure 4.3-26 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; "CO" stands for "Control"
and "CF" stands for "Configuration" in the functional constraint (FC).
Table 4.3-19 Mapping signals for SPCSO object.
Attribute
Type
orCat
orCategory
orIdent
Octet64
stVal
INT32
q
Quality
t
Timestamp
stSeld
BOOLEAN
- 757 -
FC
Signal Number
ST
522001 310A041008
ST
522001 6A0A041009
ST
522001 000A041001
ST
522001 310A041005
ST
522001 900A041006
ST
522001 000A041D90
6F2S1914 (0.49)
Signal Name
S4301_ORCAT
S4301_ORIDENT
S4301_STATE
S4301_QUALITY
S4301_TIME
S4301_STSELD
GRL200 (Soft 033 & 037)