Operation feature
4.5.1
Time accumulation process
(i)
Figure 4.5-1 outlines the time accumulation process within the TOTALTIM function. The
TOTALTIM function accumulates the time for which the state of the operating signal is in the
"ON" status every second. The accumulation process continues until the maximum
accumulated time reaches 10,000 days (almost 27 years).
Operation
signal
Cumulative
time
864,000,000sec
60sec
0sec
Acquisition of operation signal
(ii)
The user should connect the binary input circuit (BI) to the TOTALTIM function.
Figure 4.5-2 illustrates that 12 signals can be accommodated from external devices using
BIs. For example, when binary input circuit BI1 receives operating signal1, provided signal-
monitoring point "BI1" is applied for the acquisition of the signal, the user can make the logic
to connect "BI1" with TT01 of the TOTALTIM function using the PLC function.
TOTALTIM process
Figure 4.5-1 Cumulative time process
- 784 -
6F2S1914 (0.49)
The value returns to zero if the
time
counter
reaches
the
maximum value.
Operation time
The TOTALTIM function
checks the state of the
operation signal every
second. If the operation
signal is in the "On" state,
TOTALTIM accumulates
the "On" time.