Selection logic in SPOS01
"SPOS01_OSL_BO_CSF"
Select command in
SPOS01
1≥
"SPOS01_FSL_BO_CSF"
Select command OFF in
SPOS01
Figure 4.1-32 Example of select command connection with BO1
†Note: Table 4.1-26 shows the remaining signals with the excepting
"SPOS01_SL_BO_FLG".
BO connection for "operate command On/Off"
(iii)
Figure 4.1-33 exemplifies the connection for operate command On/Off. Suppose that
connections with the BOs are achieved by the PLC function using connection
point "SPOS01_OEX_BO" and "SPOS01_FEX_BO" as a result, the "Operate command On" and
the "Operate command Off" signal is issued at BO2 or BO3.
Operate logic in SPOS01
"
SPOS01_OEX_BO
(510001_8201011DD3)
Operate logic for
"Operate command
On"
To contact health
check
"
SPOS01_FEX_BO
(510001_8101011DD0)
Operate logic for
"Operate command
Off"
To contact health
check
Figure 4.1-33 Example of operate commands connected with BO2 and BO3 at IO#1
†Note: Table 4.1-27 shows the remaining signals excepting "SPOS01_OEX_BO" and
"SPOS01_FEX_BO".
"
"
SPOS01_SL_BO_FLG
(510001_8501011F76)
Connected by
"Programming"
To contact health
check
PLC connection point in BO1
"
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO2
"
200B01 310201E11D
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO3
200B01 310202E11D
- 656 -
BO1 circuit at IO#1 (Function ID: 200B01)
Signal designated by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[BO1_CPL]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
200B01 310200E11D
BO1_SOURCE
BO2 and BO3 circuit at IO#1 (Function ID: 200B01)
≥1
&
On
[BO2_CPL]
&
Off
BO2_SOURCE
(
≥1
&
On
&
[BO3_CPL]
Off
BO3_SOURCE
6F2S1914 (0.49)
Terminal and
"
"
BO1
(
200B01_8002001112)
DRIVER
BO1
&
≥1
"
"
BO1-RB
On
&
(200B01_8002001113)
Off
To contact health
check
Terminal and
wire
"
"
BO2
Operate
(200B01_8102011112)
command
On
DRIVER
BO2
≥1
"
"
BO2-RB
(
200B01_8102011113)
To contact health
check
"
"
BO3
Operate
200B01_8202021112)
command
Off
DRIVER
BO3
≥1
"
"
BO3-RB
(
200B01_8202021113)
To contact health
check
GRL200 (Soft 033 & 037)
wire
Select
command
On/Off