Toshiba GR200 Series Instruction Manual page 975

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

§§Note: The "TPOS01-PIEX-BO" signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. If the signal is to be issued from the programmed logic by
the user instead of the logic shown in Figure 4.9-26, connect the "operate
completed" signal generated in the user-programmed logic to connection point#2
"User configurable condition". That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use "TPOS01IN_TMP_38".
Output signal to BO
The TPOS01 function, in Figure 4.9-43, can issue a signal "Operate P3-control" at output point
"TPOS01_P3EX_BO", when the TPOS01 function determines that the signal "PLC-P3-Control"
is true.
Operate condition
(x)
In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.9-44 illustrates the logic to
examine
an
operate
"TPOS01_STATE". If the functionality of the original logic does not meet with user-
requirements, the following alternatives are provided:
1. The user can replace the original logic with alternative logic,
2. The user can add another signal to the original logic.
Replacing the original logic
If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connect point "User configurable operate condition".
1.
Connect the user-customized logic using "TPOS01IN_TMP_34", listed as PLC#2 in
Table 4.9-19.
2.
Set scheme switch [TPOS01-LGEXFFCT] to PLC.
Adding another operate condition signal
If the addition of another operate condition is required, the user can add the signal to operate
condition logic using PLC connection point "Additional condition".
1.
Add a user-preferred signal using "TPOS01IN_TMP_33", listed as PLC#1 in Table
4.9-19.
2.
Set scheme switch [TPOS01-LGEXFFCT] to Fixed logic.
condition.
The
operate
- 952 -
6F2S1914 (0.49)
condition
is
determined
GRL200 (Soft 033 & 037)
by
signal