Cancel logic for SBO mode
4.2.2
In the SBO control mode, the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly, the IED can discard the select command; finally, the
operation returns to the initial stage (i.e., "Wait for a command".)
Receiving "Cancel" from the remote-end
(i)
Figure 4.2-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Wait for a command
Select logics
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-14 Outline of 'cancel' command from the remote-end
Input point required mapping
Figure 4.2-15 depicts the cancel logic when a "Cancel command (Remote-Cancel)" signal is
applied to the DPSY01 function. The input-point "DEV01_CONTROL_REQ" is the same as
that for the signal "Select command Closing (Remote-Closing-Control)".
Input
Command "Remote-cancel"
511001_7002016D08
DEV01_CONTROL_REQ
†Note: The "cancel condition" logic is shown in Figure 4.2-18.
Wait for a next command
Cancel from the remote-end
Signal reception in
IEC61850
Cancel from the local-end
Operate logic
Operate command
Operate logic
DPSY01 function (Function ID: 511001)
Cancel command
Cancel condition†
Figure 4.2-15 'Cancel' from the remote-end in DPSY01
Cancel logic
510001 7001016D08
Cancel logic in DPSY01
- 686 -
6F2S1914 (0.49)
Success
Cancel
Do nothing
decision
Failed
Output
&
To "Wait for a command"
"DPSY01_ CC_SS" (511001
8602011E95)
&
Successes to cancel
"Do nothing"
"DPSY01_CC_FS"
(511001 8702011E96)
Operation Failed
GRL200 (Soft 033 & 037)