*Note: The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
Note: To identify the input and output signal-points of the DPSY02 logic, see Table
††
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
Note: The "Operate failed" signal is issued when the state-change is not detected until
‡‡
after reaching the time set by the [DPSY01-RST].
Output signal to BO
The DPSY01 function, in Figure 4.2-24, can issue an "Operate" signal at the output point
"DPSY01_OEX_BO", if the DPSY01 function determines that the signal "Local-Closing-
Control" is true.
Receiving "operate command Open" from front panel
(iv)
Figure 4.2-25 depicts the reception of the operate command for 'Open' from the front panel.
These input and output signals and the procedure are highlighted in the figure below.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-25 Outline of operate command Open
Input signal generated at the local-end
Figure 4.2-26 illustrates the operate logic when an "Operate command Open (Local-Open-
Control)" signal is applied to the DPSY01 function. The signal is generated when "Execution
for Open" is keyed on the IED front panel.
Wait for a next command
Operate command Closing from the remote-end
Operate command Open from the remote-end
Operate command Closing l from the local-end
Operate command Open from the local-end
Operate logic
Signal reception from
the front panel
Operate command Closing by the PLC function
Operate command Open by the PLC function
- 696 -
6F2S1914 (0.49)
Success
Operation
Signal output
decision
Do nothing
Failed
GRL200 (Soft 033 & 037)