Toshiba GR200 Series Instruction Manual page 385

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Detector
Operating (A)
LD1
LD2
LD3
LD4
LD5
LD6
LD7
As shown in Figure 2.29-4, the OCMFS element can operate when one or more detectors
keep operating for five seconds. The OCMFS operation will reset when all LD detectors are
reset.
Setting of OCMF
(ii)
The OCMF function is used for tripping, but it can be used for the OST alone by scheme switch
[OCMFS-EN]. When On-T is set, it operates for the trip function, whereas it will operate for
the OST alone if On-S is set for the [OCMSF-EN]. Off has to be set for the [OCMSF-EN], if the
operation of the OCMF function should be disabled.
Under-voltage element for phase-to-earth (UVFS)
2.29.5
Its element can measure a voltage of phase-to-earth. Its sensitivity is determined with setting
[UVFS]. Its operation is initiated if a phase-to-earth voltage are below the setting. On has to
be set for the scheme switch [UVFS-EN] for its operation and setting.
Under-voltage element for phase-to-phase (UVSFS)
2.29.6
Its element operates if a voltage of phase-to-phase is below setting [UVSFS]. On has to be set
for the scheme switch [UVSFS-EN] for its operation and setting.
Under-voltage change detection element (DUVFS)
2.29.7
Its element operates if a voltage is below setting [DUVFS]. Its operation is decided by the
comparison between a present voltage and a previous (i.e., 1 cycle before) voltage. Its
sensitivity is determined by the setting [DUVFS], and its off-delay timer is provided by the
setting [TDUVFS].
Table 2.29-2 Level Detector Settings
1A rating
Resetting (A)
0.10
0.08
0.16
0.13
0.26
0.21
0.41
0.33
0.66
0.53
1.05
0.84
1.68
1.34
- 362 -
5A rating
Operating (A)
Resetting (A)
0.50
0.80
1.30
2.05
3.30
5.25
8.40
6F2S1914 (0.49)
0.40
0.65
1.05
1.65
2.65
4.20
6.70
GRL200 (Soft 033 & 037)