Toshiba GR200 Series Instruction Manual page 260

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

OC (Function ID: 440001)
Setting items
TOC2R
OC2-RTMS-
ORG
OC2-k
OC2-a
OC2-c
OC2-kr
OC2-b
Output
OC2-2fBlk
OC2-VTFBlk
OC2-OPMD
OC2-UseFor
OC2-ARCBlk
OC3
OC3-Dir
OC3-Angle
OC3-Timer
DT
OC3
OC3-DPR
TOC3
IEC
OC3
OC3-DPR
OC3-TMS-IEC
TOC3R
UK
OC3
OC3-DPR
OC3-TMS-UK
TOC3R
IEEE
OC3
OC3-DPR
OC3-TMS-
IEEE
OC3-Rtimer
TOC3R
OC3-RTMS-
IEEE
US
OC3
OC3-DPR
OC3-TMS-US
OC3-Rtimer
TOC3R
OC3-RTMS-US
Range
Unit
1A rating
5A rating
0.00 - 300.00
s OC2 definite time reset delay
OC2 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
0.00000 - 500.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
Non / Block-3P /
- OC2 operation block by 2f-detection
Block-PerP
Non / Block
- OC2 operation block by VTF
3POR / 2OUTOF3
- OC2 operation mode
Trip / Alarm
- OC2 used for trip or alarm
Non / Block
- Autoreclose block by OC2
NonDir / Forward /
- OC3 directional characteristic
Reverse
0 - 180
deg OC3 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC3 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 -
0.10 -
A OC3 threshold (in DT mode)
50.00
250.00
10 - 100
% OC3 drop-out/pick-up ratio
0.00 - 300.00
s OC3 operating delay time (in DT mode)
0.02 -
0.10 -
A OC3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of IEC inverse curve
0.00 - 300.00
s OC3 definite time reset delay
0.02 -
0.10 -
A OC3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of UK inverse curve
0.00 - 300.00
s OC3 definite time reset delay
0.02 -
0.10 -
A OC3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of IEEE inverse curve
DEF / DEP
- OC3 reset delay type of IEEE
0.00 - 300.00
s OC3 definite time reset delay
OC3 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 -
0.10 -
A OC3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of US inverse curve
DEF / DEP
- OC3 reset delay type of US
0.00 - 300.00
s OC3 definite time reset delay
OC3 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
- 237 -
6F2S1914 (0.49)
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
3POR
Trip
Block
NonDir
45
DT
1.00
5.00
100
1.00
1.00
5.00
100
1.000
0.00
1.00
5.00
100
1.000
0.00
1.00
5.00
100
1.000
DEF
0.00
1.000
1.00
5.00
100
1.000
DEF
0.00
1.000