Toshiba GR200 Series Instruction Manual page 306

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.18.4
THM (Function ID: 451001)
Setting items
THM-EN
THM
TTHM
Type
THM-Itype
THM-q
SW
THMT-EN
THM-UseFor
ALM
THMA-EN
THM-Alarm
Test tool(Function ID: 451001)
Items
Function test
THM-Test
THM-IP
Range
Unit
1A rating
5A rating
Off / On
- Thermal protection scheme switch
0.40 -
2.00 -
A Thermal overload current
2.00
10.00
0.5 - 500.0
Thermal time constant
min
Max phase/
- Selection of THM equations
Equivalent
0 - 10
- Factor when Equivalent selected
Off / On
- Thermal protection
Trip / Alarm
- THM used for trip or alarm
Off / On
- Thermal alarm switch
50 - 100
% Thermal alarm level multiplier
Range
Unit
1A rating
5A rating
Off / On
- Thermal protection scheme switch
0.00 -
0.00 -
A Thermal overload current
1.00
5.00
- 283 -
6F2S1914 (0.49)
Contents
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
1.00
5.00
10.0
Equivalent
0
Off
Trip
Off
80
Default
Note
1A
5A
Off
0.00
0.00

Advertisement

Table of Contents
loading