†Note: Although the "LED_RST_COM" signal is connected previously with several LEDs,
by the manufacturer, user can also connect the signal with the LEDs. See section
3.6.4 for how to connect.
Operate condition
(iii)
Figure 3.6-8 shows the operate condition logic of the LEDR function, which is used to determine
a reset-condition for the operation.
Command blocking*1 (S4301 defines "Blocked")
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
Control hierarchy (e.g. 43RL) (PLC connection point) *5
528001 820701ED50
LEDR01_CTRL_RIGHT
IED serious error detected
Figure 3.6-8 Operate condition logic in LEDR
Note:
"Command blocking" disables all operation except for its own: the "command
*1
blocking" function is initiated by the status of "S4301" in a software controller
(SOFTSW). The IEC 61850 standard defines the "command blocking" function as
"CmdBlk". For more information on S4301, see Chapter
application: Software switch control function
Table 3.6-2.
Note:
"Double Command Blocking (DCB)" is an operation philosophy in the
*2
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as "DCB RCV_OR in Table 3.6-2. For more information, see Chapter
monitoring application: Common controls
Note:
If the event "device-travelling" is detected in the CMNCTRL function, it
*3
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
detected. The detecting signal is denoted as "Traveling OR" in Table 3.6-2.
Note:
Criteria "unmatched conditions" are decided when the "Test-bit status" in a
*4
command is not identical to the "IED test status".
Note:
The user must program the PLC logic for "Control hierarchy condition". The
*5
user must connect that to the select condition logic using the connection point
"LEDR01_CTRL_RIGHT". For more information, see chapter
LEDR function (Function ID: 528001)
S4301_STATE
DCB RCV OR
Unmatched condition detected *4
Traveling OR
Users must setup this condition correctly
SERI_ERR
[LEDDR1_EN]
On
- 581 -
6F2S1914 (0.49)
1≥
&
&
*6
Control and monitoring
. See the signal "S4301_STATE" of
.
Control and
GRL200 (Soft 033 & 037)
To operate logic
Operate condition
Control and