stage, which the ARC issues a three-phase trip signal (CB1_94TT or CB2_94TT) for the TRC
function; the ARC function abandons to reclose the CB#1 and CB#2 (ARC1 FT or ARC2 FT).
•
CB is not ready for ARC operation
•
Failure to issue ARC shot
•
ARC block command has come through PLC connection points
•
Multi-phase trip in SPAR mode
•
Evolving fault (single phase to multiphase) in SPAR and TPAR mode
•
No link within parallel lines in MPAR mode; ( final trip selected)
•
Final trip selected for 3-phase fault (user settable)
•
ARC close fail
•
Shot number over
- 425 -