Toshiba GR200 Series Instruction Manual page 974

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

switch [TPOS01-LGP3EXOT].
Input
Command "PLC-P3-Control"requiring ILK check (PLC#3
connection point)
513001 800401EE37
DEV01_P3_INTERLOCK
Command "PLC-P3-Control "not requiring ILK check
(PLC#4 connection point)
513001 800401EE36
DEV01_P3_COMMAND
ILK† condition ("P3") passed
TPOS1-P3
User configurable condition
(PLC#4 connection point)
513001 840401EE58
TPOS01IN_TMP_29
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-43 Operate 'P3-control' using the PLC function TPOS01
†Note: The ILK function can provide the criteria for operation for "P3" control.
Note: To identify the input and output signals of the other TPOS logics, see Table
††
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
‡Note: An "operate condition" signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
"operate-condition" to the logic shown in Figure 4.9-43 using connection point #4
"User configurable condition" That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and using "TPOS01IN_TMP_29".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S switch or an
ES is changed.
‡‡Note: The Operate failed" signal "is issued when a state-change remains undetected
following expiration of the setting applied to timer [TPOS01-RST].
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P3EC_OK_CSF"
(5513001 8004011E80)
Operate Cmd.
&
with ILK
condition
Operation Cmd.
without ILK
condition
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP3EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P3EC_OK_CSF"
(513001 8004011E80)
- 951 -
"
TPOS01_P3EC_OK_CS"
(513001 8404011E83)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1914 (0.49)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P3EX_BO"
(513001 8204011DD6) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(5130018004011E93)
Operation Completed
"
TPOS01_EX_FFL
[TPOS01-RST]
(513001 8604011E91) ‡‡
0
t
1.0s- 100.0s
Operation Failed
††
GRL200 (Soft 033 & 037)
"
"