Input
Command "Remote-On-Control"
511001_7002016D08
DEV01_CONTROL_REQ
ILK condition ("Open") passed
DPSY01-Open
User configurable condition
(PLC#3 connection point)
511001 800201EE56
DPSY01IN_TMP_34
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
511001 820201EE5E
DPSY01IN_TMP_44
Figure 4.2-22 'Open' operate from the remote-end in DPSY01
†Note: The ILK function can provide the operation criteria for "Open".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative "operate-condition" is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative "operate-condition" can be connected to the above logic using
connection point #3 "User-configurable condition". That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use "DPSY01IN_TMP_34".
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal "DPSY01_OEX_BO" is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The "Operate completed" signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal "Operate completed",
hence this signal is now generated by the user-programmed logic at connection
point #2 "User-configurable condition". That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use "DPSY01IN_TMP_44".
*Note: The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-16 for
††
Operate logic in DPSY01
)
DPSY01 function (Function ID: 511001
"
DPSY01_FEC_OK_CSF"
(511001 8002011E7E)
Operate Cmd.
with ILK† condition
&
Operation Cmd.
without ILK† condition
[DPSY01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPSY01-LGCFEXOT]
Fixedlogic
[DPSY01-PLSM]*
Var
Fix
Detection of state-change in a device
"DPSY01_FEC_OK_CSF"
(511001 8002011E7E)
- 693 -
"
DPYS01_FEC_OK_CS"
(511001 8002011E7E)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1914 (0.49)
Output
[DPSY01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPSY01_FEX_BO" §§
(511001 8102011DD0)
&
Assign to BOs
To "Wait for a command"
"
DPSY01_EX_CMP
(511001 8002011E93)
Operate Completed
"
DPSY01_EX_FFL
[DPSY01-RST]
(511001 8602011E91)
0
t
1.0s- 100.0s
Operate Failed
††
GRL200 (Soft 033 & 037)
"
"