Toshiba GR200 Series Instruction Manual page 720

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command "Local-Open-Control"
ILK condition ("Open") passed
DPSY01--Open
ILK bypassing
ICB_STATE
User configurable condition (PLC#3 connection point)
511001 800201EE56
DPSY01IN_TMP_34
ASEQ§ function" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
511001 820201EE5E
DPSY01IN_TMP_44
"DPSY01_FEC_OK_CSF"
(512001 8003011E7E)
†Note: The ILK function can provide the operation criteria for "Open".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative "operate-condition" is required it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative "operate-condition" can be connected to the above logic using
connection point #3 "User-configurable condition". That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use "DPSY01IN_TMP_34".
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal "DPSY01_OEX_BO" is issued when Fixlogic is set for the scheme
switch [DPSY01-LGCFEXOT]. The "Operate completed" signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.2-20. The user-programmed logic is connected internally to the signal "Operate
completed", hence this signal is now generated by the user-programmed logic at
connection point #2 "User configurable condition". That is, set the scheme switch
[DPSY01-LGCFEXOT] to PLC and use "DPSY01IN_TMP_44".
*Note: The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-16 for
††
Operate logic in DPSY01
DPSY01 function (Function ID: 511001)
Operate Cmd.
with ILK† condition
Operation Cmd.
without ILK† condition
1≥
[DPSY01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPSY01-LGCFEXOT]
Fixedlogic
[DPOS01-PLSM]
Var
Fix
Detection of state-change in a device
Figure 4.2-26 Operate Open logic at local in DPSY01
"
DPSY01_FEC_OK_CS"
(511001 8002011E7E)
1≥
&
1≥
&
&
PLC#3
&
1≥
&
PLC#2
- 697 -
6F2S1914 (0.49)
To BO connection
"
DPSY01_FEC_OK_CSF"
(511001 8002011E7E)
[DPSY01-CPW]
&
1≥
0.1 – 50.0 s
S
&
R
To BO connection
"DPSY01_FEX_BO"
(511001 8102011DD0)
&
To "Wait for a command"
"
DPSY01_EX_CMP
(
511001 8002011E93
Operation Completed
"
DPSY01_EX_FFL
[DPSY01-RST]
(511001 8602011E91)
0
t
&
1.0s- 100.0s
GRL200 (Soft 033 & 037)
Output
††
Assign to BOs
"
)
"
Operation Failed