Scheme and activation
2.35.6
VCHK1 and VCHK2 provide output signals to the ARC with results of voltage check and
synchronism check as described earlier. The energizing control scheme of VCHK1 is drawn in
Figure 2.35-10, the output signal ARC1-VCHK is fed to ARC1 when one or more of the
following conditions are established: (1) the VCHK1 runs, (2) the OVB and the UVL run, or (3)
the UVB and the OVL run. The activation of VCHK1 is controlled by using the scheme
switches: [ARC1-LB_DL], [ARC1-DB_LL], [ARC1-DB_DL], and [ARC1-SYN1]. For example,
DB_LL in Table 2.35-2 is only the criteria for ARC1 operation, On is set for the scheme switch
[ARC1-DB_LL] while Off is set for other scheme switches. As a result, the system is energized
in the direction from line to bus with ARC1. As shown in Figure 2.35-11, the operation of the
VCHK2 is also applicable in accordance with Figure 2.35-3 similar to VCHK1. Note that the
SYN1-df and SYN2-df operations are nullified when Off are set for the [SYN1-dfEN] and
[SYN2-dfEN].
OVB
8200011B62
OVB
8000011B63
UVB
8300011B60
OVL
OVL
8C00011B67
L1
&
8D00011B68
OVL
L2
8E00011B69
L3
8100011B61
UVL
UVL
OVB
OVL
8400011B64
SYN1-dƟ
8500011B65
SYN1-dV
8600011B66
SYN1-df
SYN1-dfEN
OFF
T_LB_DL
t
0
&
0.01-100.00S
ARC1-LB_DL
T_DB_LL
t
0
&
0.01-100.00S
T_OVL3P
t
0
0.01-100.00S
T_DB_DL
t
0
&
0.01-100.00S
8300011B71
T_SYN1
&
t
0
0.01-100.00S
ARC1-SYN1
ARC1-NOVCHK
≥1
Figure 2.35-10 Logic of VCHK1
- 489 -
8000011B6D
&
ON
8100011B6E
&
ARC1-DB_LL
ON
8F00011B6F
VCHK_OVL3P
8200011B70
&
ARC1-DB_DL
ON
8300011B72
&
ON
ON
6F2S1914 (0.49)
8000011B23
≥1
ARC1-VCHK
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents