Toshiba GR200 Series Instruction Manual page 28

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Busbar R
N
Trip command
Relay
(N)
Main (primary)
DIF
(N)
Backup (local)
Delay timer
Zone1 in ZS
(N)
t
t
OC
(N)
t
EF
(N)
Backup (remote)
t
Zone2 in ZS
(N)
Fail safe (FS) relay
(N)
t
0
Extra FS relay
Figure 1.1-3 Protection zones provided by the main relay and backup relays
†Note: When the carrier command protection function (DISCAR or DEFCAR) is
available, the function can also service as a local backup protection. We shall also
note that the function cannot operate in the device failure in the
telecommunication.
Coordination between the main and the backup protections
(ii)
The operation of the backup protection is realized by retarding the operation of the backup
protection rather than the main protection; retarding is made with setting the delay timer of
the backup protection. We shall note that the setting value for the delay timer should be chosen
so that the coordination between the main protection and the backup protection is realized.
The degree for retarding the backup protection is determined by the consideration of operating
and reset time margins:
• Operating time of the main protection
• Reset time of backup protections
• Operating time of the circuit breaker
Types of the backup protections
(iii)
The backup protections are grouped into two: 1.backup protections serviced from the remote
end far from the location of the main protection and 2.backup protections serviced locally as
same as the main protection.
Zone2
(N)
Zone1
(N)
DIF
(N)
Tele communication
TRC
0
0
&
0
0
- 5 -
Busbar G
M
O
Relay
(O)
Relay
(M)
DIF
(O)
Zone1 in ZS
(O)
OC
(O)
EF
(O)
Zone2 in ZS
(O)
Fail safe (FS)
(O)
6F2S1914 (0.49)
Busbar H
Line
K
Relay
(K)
GRL200 (Soft 033 & 037)
Relay
(
Zone1 in
OC
(M)
EF
(M)
Zone2 in
Fail safe (
Extra F