Toshiba GR200 Series Instruction Manual page 964

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command Local-P1-Control"
513001_7004016D08
DEV01_CONTROL_REQ
ILK† condition ("P1") passed
TPOS1-P1
ILK† bypassing
ICB_STATE
User configurable condition (PLC#3 connection point)
513001 810401EE57
TPOS01IN_TMP_28
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-33 Operate 'P1-control' on the front panel TPOS01
†Note: The ILK function can provide the operation criteria for "P1" control.
‡Note: An "operate condition" signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition" is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative "operate-condition" can be connected to the above logic using
connection point #3 "User configurable condition" That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use "TPOS01IN_TMP_28".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
Note: To identify the input and output signal-points of the P1-control in the other TPOS
††
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The "Operate failed" signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
Operate Cmd.
with ILK
condition
&
Operate Cmd.
without ILK
condition
1≥
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP1EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
- 941 -
"
TPOS01_P1EC_OK_CS"
(5130018004011E81)
1≥
1≥
&
&
&
&
PLC#3
&
1≥
&
PLC#2
&
6F2S1914 (0.49)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P1EX_BO"
(5130018104011DD0) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
"
TPOS01_EX_FFL
[TPOS01-RST]
(513001 8604011E91) ‡‡
0
t
1.0s- 100.0s
Operate Failed
††
GRL200 (Soft 033 & 037)
"
"