Signal monitoring point
PROT_COMMON(48A001)
Element ID
8700001B9A
8300001B8B
8700001B8F
8800001B90
8900001B91
8000001B9C
8E00001B85
8C00001B9B
8C00001BBD
8C00001BB6
8F00001B86
8000001B66
8000001B6F
8100001B67
8100001B70
8200001B68
8200001B71
8000001B60
8900001B6B
8100001B61
8200001B62
8800001B6A
8400001B63
8D00001B6D
8500001B64
8600001B65
8C00001B6C
2200001BAD
3000001BA5
Connection point in PLC logic
PROT_COMMON (48A001)
Element ID
800000EBB7
800000EBB0
810000EBB8
810000EBB1
820000EBB9
820000EBB2
830000EBBF
830000EBBE
840000EBBA
840000EBB3
850000EBBB
850000EBB4
Name
Description
CB2_FAIL
States of the CB2 not to be defined in three-phase
CB_ALLPH_CLOSE
Three-phase contacts closed in CB
CB_ALLPH_OPEN
Three-phase contacts not closed in CB
CB_ANYPH_CLOSE
Any one of three-phase contacts closed in CB
CB_LOSS_PHASE
Any one of three-phase contacts opening in CB
DEAD_LINE_DETECT
Detected the line not being energized
DS_CLOSE
Main contacts closed in DS
DS_FAIL
States of the DS not to be defined
DS_NC_CONT
Aux normally-close-contact in DS
DS_NO_CONT
Aux normally-open-contact in DS
DS_OPEN
Main contact opening in DS
OCD-A
OCD element operated in phase-A
OCD-AT
Off-delay timer after OCD element in phase-A
OCD-B
OCD element operated in phase-B
OCD-BT
Off-delay timer after OCD element in phase-B
OCD-C
OCD element operated in phase-C
OCD-CT
Off-delay timer after OCD element in phase-C
UVLG-A
UVLG element operated in phase-A
UVLG-AND
UVLG elements operated in three-phase
UVLG-B
UVLG element operated in phase-B
UVLG-C
UVLG element operated in phase-C
UVLG-OR
Any UVLG element operated in three-phases
UVLS-AB
UVLS elements operated in phase-AB
UVLS-AND
UVLS elements operated in three-phase
UVLS-BC
UVLS elements operated in phase-BC
UVLS-CA
UVLS elements operated in phase-CA
UVLS-OR
Any UVLS element operated in three-phase
CB2_OPCNT
Aux normally-close-contact in three-phase of CB2
CB2_POS
Aux normally-open-contact in three-phase of CB2
Name
Description
CB1-A_NC_CONT
CB1-A normally close contact
CB1-A_NO_CONT
CB1-A normally open contact
CB1-B_NC_CONT
CB1-B normally close contact
CB1-B_NO_CONT
CB1-B normally open contact
CB1-C_NC_CONT
CB1-C normally close contact
CB1-C_NO_CONT
CB1-C normally open contact
CB1_NC_CONT
CB1 normally close contact
CB1_NO_CONT
CB1 normally open contact
CB2-A_NC_CONT
CB2-A normally close contact
CB2-A_NO_CONT
CB2-A normally open contact
CB2-B_NC_CONT
CB2-B normally close contact
CB2-B_NO_CONT
CB2-B normally open contact