Toshiba GR200 Series Instruction Manual page 242

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.14.2
SOTF-OC(Function ID: 454001)
Setting items
SOTFOC-EN
OCSOTF
OCSOTF-2fBlk
Test tool (Function ID: 454001)
Item
Function test
SOTF-Test
Data ID
2.14.3
Monitoring point for operation
SOTF-OC(Function ID: 454001)
Element ID
8000001BB2
8000001B67
8000001BB1
8000001C20
8100001C21
8200001C22
8000001B60
8000001B66
8800001B62
8900001B63
8A00001B64
8300001B23
8000001BB0
8000001B65
Connection point on PLC logic
SOTF-OC(Function ID: 454001)
Element ID
800000EBB2
800000EBB1
800000EBB0
Range
Unit
1A rating
5A rating
Off / On
- SOTF-OC protection enable
0.02 -
0.10 -
A OC relay for SOTF threshold
3.00
15.00
Non / Block-3P /
- OCSOTF operation block by 2f-detection
Block-PerP
Range
Unit
1A rating
5A rating
Off / On
- Test cold load state given with setting
Name
Description
ADD.SOTF_EN
Additional SOTFOC enable
OC-RETRIP
OC-RETRIP
OC-RTP.EN
OC-retrip enable
OCSOTF-A
SOTFOC relay element operated (phase-A)
OCSOTF-B
SOTFOC relay element operated (phase-B)
OCSOTF-C
SOTFOC relay element operated (phase-C)
OCSOTF-OR
SOTFOC relay element operated (3-phases OR)
SOTFOC-OPT
SOTFOC protection operated (3-phases OR)
SOTFOC-OPT-A
SOTFOC protection operated (phase-A)
SOTFOC-OPT-B
SOTFOC protection operated (phase-B)
SOTFOC-OPT-C
SOTFOC protection operated (phase-C)
SOTFOC-TRIP
Trip signal by SOTFOC protection operation
SOTFOC_BLOCK
SOTFOC protection block command
SOTF_EN_COND
SOTFOC protection operated permit
Name
Description
ADD.SOTF_EN
Additional SOTFOC enable
OC-RTP.EN
OC-retrip enable
SOTFOC_BLOCK
SOTFOC protection block command
- 219 -
6F2S1914 (0.49)
Contents
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
1.20
6.00
Non
Default
Note
1A
5A
Off

Advertisement

Table of Contents
loading

Table of Contents