Toshiba GR200 Series Instruction Manual page 466

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Fault current
Closed
CB#1 Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1 SHOT1
Dead time [TTPAR1]
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
ARC1 CLOSE
COMMAND
Closed
CB1 ALLPH
Open
CLOSE
ARC1 CLOSE SUCCESS
ARC1 CLOSE FAIL
Lock out
ARC1 FT
Figure 2.34-10 Multi shot scheme [ARC-NUM]=S3 for a Permanent fault
Note:
1. The permissive signal 'ARC1-VCHK' is required for ARC SHOT1 operation, but has
been omitted for clarity in this figure.
2. 'ARC1-VCHK' permissive signal is introduced automatically in the TPAR mode. For
ARC-SHOT2 and onwards, the user must introduce the permissive signal from the
VCHK function by using PLC programming.
Autoreclosing logics
2.34.5
Setting logic for ARC1 mode – setting (ARC1-MODE)
(i)
The ARC1-MODE input setting is illustrated in Figure 2.34-11. The scheme switch [ARC1-
MODE] has seven setting modes as OFF, FT, SPAR, TPAR, SPAR&TPAR, MPAR, and Original.
Dead time [TD_MS2]
[TCCW1]
)
- 443 -
Dead time [TD_MS3]
[TCCW1]
)
6F2S1914 (0.49)
[TCCW1]
)
GRL200 (Soft 033 & 037)