‡Note: The measurements in the DPOS and the DPSY functions are grouped into four
intervals in each respective device. Measurement is possible by sensing the device
events. The measured intervals are accumulated; they are grouped into four
intervals (OT1–OT4), which the user can monitor from the IED screen. Figure
4.4-2 and Figure 4.4-3 exemplify the four intervals upon occurrence of On
(Closing)-control event and Off (Open)-control event, provided that the DPOS
function operates.
Issuing Off control
intermediate state
Device status for "Off"
Figure 4.4-2 Two intervals (OT1 and OT2) for Off-control event
Issuing On control
intermediate state
Device status for "On"
Figure 4.4-3 Two intervals (OT3 and OT4) for On-control event
Tips: If the user wishes to implement the OPTIM function quickly, go to section 4.4.4,
which discusses how to map signal-points for the IEC 61850 communication.
─────────────────────────────────────────────────────────────────
Note:
The implementation of such features depends on the selection of hardware and the
configuration of functions. Several IED models do not have its features. To determine whether
its features are implemented in the IED, locate the IED ordering number; and check the order
number at the "G&T position" referring to the comparison table below. For more information,
Appendix: Ordering
see
Table 4.4-1 Comparative table in respective ordering numbers
✓: Applicable
Sensing
On
OT1
Sensing
Off
OT3
.
Sec.
Feature
Main features
NA: Not applicable
Intermediate
OT2
Intermediate
OT4
Ordering No. at "G&T"
33
37
NA
- 770 -
6F2S1914 (0.49)
Off
On
GRL200 (Soft 033 & 037)