Signal name and number
(xi)
Note: The user should note that the following descriptions shown in the column "M/O"
for each table:
"O" indicates that the signal is provided for the optional usage.
"M" indicates that the user should map/set/configure the signal; otherwise, the
"N/A" indicates that the user cannot change the state of the signal.
Table 4.9-2 PLC connection points (Input points for 'P1-control')
Signal Number
Signal Name
513001 800401EE31
DEV01_P1_INTERLOCK
513001 800402EE31
DEV02_P1_INTERLOCK
513001 800403EE31
DEV03_P1_INTERLOCK
...
....
513001 800418EE31
DEV24_P1_INTERLOCK
513001 800401EE30
DEV01_P1_COMMAND
513001 800402EE30
DEV02_P1_COMMAND
513001 800403EE30
DEV03_P1_COMMAND
....
....
513001 800418EE30
DEV24_P1_COMMAND
Table 4.9-3 PLC connection points (Input point for 'P2-control')
Signal Number
Signal Name
513001 800401EE33
DEV01_P2_INTERLOCK
513001 800402EE33
DEV02_P2_INTERLOCK
513001 800403EE33
DEV03_P2_INTERLOCK
...
....
513001 800418EE33
DEV24_P2_INTERLOCK
513001 800401EE32
DEV01_P2_COMMAND
513001 800402EE32
DEV02_P2_COMMAND
513001 800403EE32
DEV03_P2_COMMAND
....
....
513001 800418EE32
DEV24_P2_COMMAND
Table 4.9-4 PLC connection points (Input point for 'P3-control')
Signal Number
Signal Name
513001 800401EE37
DEV01_P3_INTERLOCK
513001 800402EE37
DEV02_P3_INTERLOCK
513001 800403EE37
DEV03_P3_INTERLOCK
...
....
513001 800418EE37
DEV24_P3_INTERLOCK
513001 800401EE36
DEV01_P3_COMMAND
513001 800402EE36
DEV02_P3_COMMAND
513001 800403EE36
DEV03_P3_COMMAND
....
....
513001 800418EE36
DEV24_P3_COMMAND
user may face an operational failure if the default settings are used.
Description
P1-control checking with interlock in TPOS01 (for PLC#1)
P1-control checking with interlock in TPOS02 (for PLC#1)
P1-control checking with interlock in TPOS03 (for PLC#1)
....
P1-control checking with interlock in TPOS24 (for PLC#1)
P1-control without checking in TPOS01 (for PLC#2)
P1-control without checking in TPOS02 (for PLC#2)
P1-control without checking in TPOS03 (for PLC#2)
....
P1-control without checking in TPOS24 (for PLC#2)
Description
P2-control checking with interlock in TPOS01 (for PLC#1)
P2-control checking with interlock in TPOS02 (for PLC#1)
P2-control checking with interlock in TPOS03 (for PLC#1)
....
P2-control checking with interlock in TPOS24 (for PLC#1)
P2-control without checking in TPOS01 (for PLC#2)
P2-control without checking in TPOS02 (for PLC#2)
P2-control without checking in TPOS03 (for PLC#2)
....
P2-control without checking in TPOS24 (for PLC#2)
Description
P3-control checking with interlock in TPOS01 (for PLC#1)
P3-control checking with interlock in TPOS02 (for PLC#1)
P3-control checking with interlock in TPOS03 (for PLC#1)
....
P3-control checking with interlock in TPOS24 (for PLC#1)
P3-control without checking in TPOS01 (for PLC#2)
P3-control without checking in TPOS02 (for PLC#2)
P3-control without checking in TPOS03 (for PLC#2)
....
P3-control without checking in TPOS24 (for PLC#2)
- 927 -
6F2S1914 (0.49)
M/O
O
O
O
O
O
O
O
O
M/O
O
O
O
O
O
O
O
M/O
O
O
O
O
O
O
O
O
GRL200 (Soft 033 & 037)