‡Note: An "operate condition" is generated in the operate-condition logic( see Figure
4.1-29) when Fixlogic is set for scheme switch[SPOS01-LGCTRCON], If an
alternative "Operate-condition" is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative "Operate-condition" can be connected to the above logic using
connection point #3 "User configurable condition". That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use SPOS01IN_TMP_34.
Note: The "Operate failed" signal is issued when the state-change is not detected when
‡‡
the time set by [SPOS01-RST] has been reached.
§§Note: The signal "SPOS01_OEX-BO" is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The "Operate completed "signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal "Operate completed".
Hence, this signal is now generated by the user-programmed logic at connection
point # 2 "user-configurable condition". That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use "SPOS01IN_TMP_42".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of the output signal. When Var is set for scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
"Command Off".
Note: To identify the input and output signal-points of the other SPOS logics, see Table
††
4.1-14, Table 4.1-15, Table 4.1-19, and Table 4.1-20.
Output signal to BO
The SPOS01 function, in Figure 4.1-22, can issue an "Operate" signal at the output-point
"SPOS01_FEX_BO", when the SPOS01 function determines that the signal "Remote-Off-
Control" is true.
Receiving "operate command On" from the local-end
(iii)
Figure 4.1-23 depicts the reception of the operate command for 'On' from the local-end.
- 643 -
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)