Setting
2.39.2
CLP(Function ID: 481001) at Common
Setting items
CLP-EN
CLP
CLP-SG
TCLP-EN
TCLP-RESET
DOEN
CLP-DOEN
OCCLP
TCLP-DO
Test tool(Function ID: 481001)
Item
Function test
CLP-Test
Range
Unit
1A rating
5A rating
Off / On
- Cold load protection scheme switch
Group1 / Group2 /
Group3 / Group4 /
- Applied setting group at cold load mode
Group5 / Group6 /
Group7 / Group8
0 - 10000
s Cold load enable time
0 - 10000
s Cold load reset time
Off / On
- Cold load drop-out enable
0.02 -
0.10 -
A Cold load drop-out current threshold
3.00
15.00
0.00 - 100.00
s Cold load drop-out time
Range
Unit
1A rating
5A rating
Off / STATE0 /
- Forcibly changing to CLP state
STATE3
- 549 -
6F2S1914 (0.49)
Contents
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
Group1
100
100
Off
0.50
2.50
0.00
Default
Note
1A
5A
Off