Figure 2.6-7 exemplifies the IEEE C37.94 frame format; we should map the SCOM4-SA0
bit for sending the signal "DIFGL".
a. Sending frames for remote IE Ds in IEE E C37.94
N=1
b. Connections for sending using PLC function
From DIFGL
8000001C23
DIFGL
DIFGL function
N=2
N=3
Figure 2.6-7 Mapping for sending signal using SCOM bit†
†Note: For more information, see
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].
Reception of DIFGL-operation signal from the remote
Figure 2.6-8 shows the TFC reception logic; PLC connection point "R1.DIFGL_OP" is used for
the signal receiving from the Remote-1_IED, another PLC connection point "R2.DIFGL_OP"
is used from the Remote-2_IED.
Header
I 0
Ia
SCOM1
MS0
SA0
RA0
SA1
MS0
SA2
RA3
SA3
MS0
SA4
Spare
SA5
MS0
SA6
RA0
SA7
MS0
SA8
RA3
SA9
MS0
SA10
Spare
SA11
800211EBB0
SCOM4-SA0_S
COMM_ APPL function (Function ID: 4A9001)
Header
Ia2
Header
Ia3
Chapter Relay application: Communication application
- 64 -
SCOM
V
Ib
SCOM2
SCOM3
SCOM4
MS1
MS2
RA1
RA2
MS1
MS2
RA4
RA5
MS1
MS2
Spare
Spare
MS1
MS2
RA1
RA2
Local test
MS1
MS2
RA4
RA5
MS1
MS2
Spare
Spare
Ib2
Ic2
Ib3
Ic3
COM5
6F2S1914 (0.49)
Ic
CR C
I 0
CR C
CR C
GRL200 (Soft 033 & 037)
.