Toshiba GR200 Series Instruction Manual page 762

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Output signal for monitoring
The user can monitor a "Select success" signal at the output point "S4301_OSL_CSF", when
the SOFTSW1 function determines that the received "Remote-ON-Control" signal is true. If
the SOFTSW1 function determines that the "Remote-ON-Control" is not true, the SOFTSW1
function returns to the "Wait for a command" stage.
Receiving "select command for Off operation" from the remote end
(ii)
Input point required mapping
Figure 4.3-7 shows the logic when a "Select command (Remote-OFF-Control)" signal is applied
at the SOFTSW1 function. The input-point "S4301_CONTROL_REQ" is used for the reception
of the select command (Remote-OFF-Control).
Input
Command "Remote-Off-Control"
522001_700A046D08
S4301_CONTROL_REQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function (AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.3-7 Select logic for 'OFF' operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note: "Select condition" signal is provided in Figure 4.3-12.
Output signal for monitoring
The SOFTSW1 function, in Figure 4.3-7, can issue a "Select success" signal at output point
"S4301_FSL_CSF" when the SOFTSW1 function determines that the input signal "Select
command (Remote-OFF-Control)" is true. If the SOFTSW1 function determines that the
"Remote-OFF-Control" is not true, the SOFTSW1 function returns to the "Wait for a command"
stage.
Receiving "Selection command for On operation" from the front
(iii)
Select logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
For SBO operation
Select command
For DIR operation
Operate command
In SBO operate
In DIR operate
Select condition‡
- 739 -
1≥
&
&
&
0
0
6F2S1914 (0.49)
Output
For monitoring
"S4301_FSD_CSF"
(522001_8D0A041F45)
t
Select "success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
GRL200 (Soft 033 & 037)