Toshiba GR200 Series Instruction Manual page 655

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Signal Number
Signal Name
510001 800103EE33
DEV03_CL_INTERLOCK
....
....
510001 800114EE33
DEV20_CL_INTERLOCK
Table 4.1-3 PLC connection points (Input points for command 'Off')
Signal Number
Signal Name
510001 800101EE31
DEV01_OP_INTERLOCK
510001 800102EE31
DEV02_OP_INTERLOCK
510001 800103EE31
DEV03_OP_INTERLOCK
....
....
510001 800114EE31
DEV20_OP_INTERLOCK
510001 800101EE30
DEV01_OP_COMMAND
510001 800102EE30
DEV02_OP_COMMAND
510001 800103EE30
DEV03_OP_COMMAND
....
....
510001 800114EE30
DEV20_OP_COMMAND
Table 4.1-4 PLC connection points (Interlock for command 'On/Off')
Signal Number
Signal Name
570001 3101011DA0
SPOS01-Off
570001 3101021DA0
SPOS02-Off
570001 3101031DA0
SPOS03-Off
....
....
570001 3101141DA0
SPOS020-Off
570001 3101011DA2
SPOS01-On
570001 3101021DA2
SPOS02-On
570001 3101031DA2
SPOS03-On
....
....
570001 3101141DA2
SPOS20-On
Table 4.1-5 Mapping points for the reception of control commands
Signal Number
Signal Name
510001 7001016D08
DEV01_CONTROL_REQ
510001 7001026D08
DEV02_CONTROL_REQ
510001 7001036D08
DEV03_CONTROL_REQ
....
....
510001 7001146D08
DEV20_CONTROL_REQ
Signal Number
Signal Name
522001 000A011001
CBK_STATE
522001 000A021001
ICB_STATE
523001 000D001F40
ASEQ_MULTI_SEL
5A0001 0008001F41
DCB RCV OR
5A0001 0008001F40
Traveling OR
4A0001 8300001B6F
GEN.TRIP
5A0001 3108003F40
SDCEN
5A0101 3100001F43
SERI_ERR
523001 000D001F40
ASEQ_MULTI_SEL
Description
SPOS03 PLC On-control checking with interlock
....
SPOS20 PLC On-control checking with interlock
Description
SPOS01 PLC Off-control checking with interlock
SPOS02 PLC Off-control checking with interlock
SPOS03 PLC Off-control checking with interlock
....
SPOS20 PLC Off-control checking with interlock
SPOS01 PLC Off-control without checking
SPOS02 PLC Off-control without checking
SPOS03 PLC Off-control without checking
....
SPOS20 PLC Off-control without checking
Description
SPOS01 interlock condition for Off control.
SPOS02 interlock condition for Off control.
SPOS03 interlock condition for Off control.
....
SPOS20 interlock condition for Off control.
SPOS01 interlock condition for On control.
SPOS02 interlock condition for On control.
SPOS03 interlock condition for On control.
....
SPOS20 interlock condition for On control.
Description
SPOS01 control command received. (Mapping Data)
SPOS02 control command received. (Mapping Data)
SPOS03 control command received. (Mapping Data)
....
SPOS20 control command received. (Mapping Data)
Table 4.1-6 Input signals to condition logic
Description
Command Blocking status ( Off / Blocked)
Interlock bypassing status(On / Bypass)
Automatic sequence control is in progress.
Double Command Blocking(DCB) is in progress.
Travelling events are detected.
General trip
(This is setting of CMNCTRL)
Serious Error detected
Automatic sequence control is in progress.
- 632 -
6F2S1914 (0.49)
M/O
O
O
M/O
O
O
O
O
O
O
O
O
M/O
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
M/O
M
M
M
M
M/O
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
GRL200 (Soft 033 & 037)