OCN(Function ID:443001)
Setting items
OCN2-RTMS-
US
ORG
OCN2
OCN2-DPR
OCN2-TMS-
ORG
OCN2-Rtimer
TOCN2R
OCN2-RTMS-
ORG
OCN2-k
OCN2-a
OCN2-c
OCN2-kr
OCN2-b
Output
OCN2-2fBlk
OCN2-VTFBlk
OCN2-CTFBlk
OCN2-UseFor
OCN2-ARCBlk
OCN3
OCN3-Dir
Fwd/
OCN3-Angle
Rev
OCN3-Vpol
OCN3-Timer
DT
OCN3
OCN3-DPR
TOCN3
IEC
OCN3
OCN3-DPR
OCN3-TMS-
IEC
TOCN3R
UK
OCN3
OCN3-DPR
OCN3-TMS-
UK
TOCN3R
IEEE
OCN3
OCN3-DPR
OCN3-TMS-
IEEE
OCN3-Rtimer
TOCN3R
Range
Unit
1A rating
5A rating
OCN2 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 -
0.10 -
A OCN2 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of US inverse curve
DEF / DEP
- OCN2 reset delay type of ORG
0.00 - 300.00
s OCN2 definite time reset delay
OCN2 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OCN2 user original curve coefficient
0.00000 - 10.00000
- OCN2 user original curve coefficient
0.00000 - 10.00000
- OCN2 user original curve coefficient
0.00000 - 500.00000
- OCN2 user original curve coefficient
0.00000 - 10.00000
- OCN2 user original curve coefficient
Non / Block
- OCN2 operation block by 2f-detection
Non / Block
- OCN2 operation block by VTF
Non / Block
- OCN2 operation block by CTF
Trip / Alarm
- OCN2 used for trip or alarm
Non / Block
- Autoreclose block by OCN2
NonDir / Forward /
- OCN3 directional characteristic
Reverse
0 - 180
deg OCN3 directional characteristic angle
0.5 - 25.0
V OCN3 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OCN3 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 -
0.10 -
A OCN3 threshold (in DT mode)
50.00
250.00
10 - 100
% OCN3 drop-out/pick-up ratio
0.00 - 300.00
s OCN3 operating delay time
0.02 -
0.10 -
A OCN3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN3 drop-out/pick-up ratio
0.010 - 50.000
- OCN3 time multiplier of IEC inverse curve
0.00 - 300.00
s OCN3 definite time reset delay
0.02 -
0.10 -
A OCN3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN3 drop-out/pick-up ratio
0.010 - 50.000
- OCN3 time multiplier of UK inverse curve
0.00 - 300.00
s OCN3 definite time reset delay
0.02 -
0.10 -
A OCN3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN3 drop-out/pick-up ratio
0.010 - 50.000
- OCN3 time multiplier of IEEE inverse curve
DEF / DEP
- OCN3 reset delay type of IEEE
0.00 - 300.00
s OCN3 definite time reset delay
- 274 -
6F2S1914 (0.49)
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
1.000
0.40
2.00
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Non
Trip
Block
NonDir
45
3.0
DT
0.40
2.00
100
1.00
0.40
2.00
100
1.000
0.00
0.40
2.00
100
1.000
0.00
0.40
2.00
100
1.000
DEF
0.00