Toshiba GR200 Series Instruction Manual page 936

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command "P3-Control" from the remote
513001 7004016D08
DEV01_CONTROL_REQ
ILK† condition ("P3") passed
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function (AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.9-7 Select 'P3-control' from the remote-end in TPOS01
†Note: The ILK function provides the operation criteria for "P3 control".
Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
††
Table 4.9-7 and Table 4.9-10.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
Output signal to BO
The TPOS01 function, in Figure 4.9-7, can issue a signal "Select success" at the output point
"TPOS01_P3SL_BO_FL" when the TPOS01 function determines that the received signal
"Select command P3 (Remote-P3-Control)" is true. If the TPOS01 function determines that the
"Remote-P3-Control" is not true, the TPOS01 function returns to the "Wait for a command"
stage.
TPOS01 function (Function ID: 513001)
For SBO operation
Select command
with ILK† condition
For DIR operation
Operate command
with ILK† condition
TPOS1-P3
For SBO operation
Select command
without ILK† condition
For DIR operation
Operate command
without ILK† condition
In SBO operate
In DIR operate
Select condition‡
- 913 -
Selection logic in TPOS01
1≥
&
&
&
&
6F2S1914 (0.49)
Output
&
To BO connection
"TPOS01_P3SL_BO_FLG"
(513001 8A04011DC8)
0
t
Select "success"
0.1s
To "Wait for a command"
t
0
Select "Failed"
0.6s
††
.
GRL200 (Soft 033 & 037)