Cancel logic for SBO mode
4.9.2
In the SBO control mode, the reception of a cancel command can be possible when the cancel
conditions are satisfied, the function can discard the select command; finally, the operation
returns to the initial stage (i.e., "wait for a command").
Receiving "Cancel" from the remote-end
(i)
Figure 4.9-21 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Wait for a command
Select stage
P1 control from the remote-end
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Figure 4.9-21 Outline of 'cancel' command from remote-end
Input point required mapping
Figure 4.9-22 depicts the cancel logic when a "Cancel command (Remote-Cancel)" signal is
applied to the TPOS01 function. The input-point "DEV01_CONTROL_REQ" is the same as
that for the "Selection command P1 (Remote-P1-Control)" signal.
Input
Command "Remote-cancel"
513001_7004016D08
DEV01_CONTROL_REQ
Figure 4.9-22 'Cancel' from the remote-end in TPOS01
†Note: The logic "cancel condition" is shown in Figure 4.9-25.
Output signal to BO
Wait for a next command
Cancel from remote-end
Signal reception in
IEC61850
Cancel from the local-end
Operate logic
Operate command
Operate logic
510001 7001016D08
Cancel logic in TPOS01
TPOS01 function (Function ID: 513001)
Cancel command
Cancel condition†
- 930 -
Success
Cancel
Cancel logic
decision
&
&
6F2S1914 (0.49)
Do nothing
Failed
Output
To "Wait for a command"
"TPOS01_ CC_SS"
(513001_8604011E95)
Successes to cancel
"Do nothing"
"TPOS01_CC_FS"
(513001_8704011E96)
Operation Failed