Toshiba GR200 Series Instruction Manual page 763

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

panel
Input signal
Figure 4.3-8 shows the logic when a "Select command (Local-ON-Control)" signal is applied to
the SOFTSW1 function. The input signal is provided when "On" key is pressed on the IED
front panel; the input-point is not required to be mapped. Note that the user should set scheme
switch [S4301-CTRAHMI] to SBO when the operation from the IED front panel is performed;
User interface: Control sub-menu
chapter
Input
Command "Local-On-Control"
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function (AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.3-8 Select logic for 'ON' operation at the IED locally in SOFTSW1†
†Note: To identify the output points of the other SOFTSW logics, see Table 4.3-9.
‡Note: Signal "select condition" is provided. See Figure 4.3-12.
§Note: The SOFTSW1 function is blocked when the ASEQ function is in operation.
Output signal for monitoring
When the state of "select condition" is true, the SOFTSW1 function can issue an output signal
"Select success" at the output-point "S4301_OSD_CSF".
Note: The signal "S4301_OSD_CSF" is the same signal as shown in Figure 4.3-6. If the
input signal "Local-ON-Control" is not true, the SOFTSW1 function returns to the
"Wait for a command" stage.
Receiving "Select command for Off operation" from the front panel
(iv)
Input signal
Figure 4.3-9 shows the logic when a "Select command (Local-OFF-Control)" signal is applied
to the SOFTSW1 logic. The input signal is provided when the user presses "OFF" key on the
IED front panel; the input-point is not required to be mapped.
discusses how to operate.
Select logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
For SBO operation
Select command
For DIR operation
Operate command
[S4301-CTRAHMI]
SBO
Select condition‡
- 740 -
1≥
&
&
SBO
&
DIR
6F2S1914 (0.49)
Output
For monitoring
"S4301_OSD_CSF"
(522001_8F0A041F49)
0
t
Select "success"
0.1s
To "Wait for a command"
0
t
Select "Failed"
0.6s