Toshiba GR200 Series Instruction Manual page 948

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

How to add another select condition signal
If adding another condition is required, the user can add a signal to the select condition logic
using the PLC condition point "User Additional Condition".
1.
Add a user-preferred signal using TPOS01IN_TMP_24, which is listed as PLC#1 in
Table 4.9-8.
2.
Set the scheme switch [TPOS01-LGSLFFCT] to Fixed logic.
Command blocking*1
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
Tripping *4 ("General trip")
Additional condition (PLC#1 connection point)
513001 800401EE61
TPOS01IN_TMP_24
User configurable condition (PLC#2 connection point)
513001 810401EE62
TPOS01IN_TMP_25
Control hierarchy (e.g. 43RL) (PLC#3 connection point) *10
513001 820401ED50
TPOS01IN_TMP_21
IED serious error detected
Figure 4.9-20 Select condition logic for 'P1–P3 control' in TPOS01*
Note:
*1
blocking" is initiated by the status of "CBK" in a software switch controller
(SOFTSW). The IEC 61850 standard defines "Command Blocking" as "CmdBlk".
For more information of "CBK", see Chapter
Software switch control
Note:
*2
to protect the substation. The user can program it using GR-TIEMS.
TPOS01 function (Function ID: 513001)
CBK_STATE
DCB RCV OR
Unmatched condition detected *5
Traveling OR
Event suppression detected *6
= TPOS01_QLT_SPP
BI board connection error detected*7
GEN. TRIP
= TPOS01_QLT_BI_ERR
[SCDEN]*8
OFF
P1-control command received
(513001 8304011D02)
TPOS01_ST_P1
P2-control command received
(513001 8104011D03)
TPOS01_ST_P2
P3-control command received
(513001 8504011D04)
TPOS01_ST_P3
[TPOS01-DEVTYPE]*9
EDS
[TPOS01-LGSLFFCT]
Fixedlogic
Users must setup this condition correctly
SERI_ERR
[TPOS01-CTREN]
On
"Command Blocking" disables any operation except its own; the "Command
. See the signal "CBK_STATE" of Table 4.9-6.
"Double Command Blocking (DCB)" is an operation philosophy. It can be used
1≥
(513001 8204011F59)
(513001 8604011F5A)
&
&
&
&
&
Control and monitoring application:
- 925 -
6F2S1914 (0.49)
1≥
&
&
To selection logic
Select condition
Same Directional
Controlling Event
"EDS" never permit to control
from "P1 to P3" and "P3 to P1".
&
&
11
GRL200 (Soft 033 & 037)