Toshiba GR200 Series Instruction Manual page 736

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Signals from the
BI circuit and DPSY01
devices
Phase-A signals
BI signal selected by
setting [DPSY01A-NOPSG]
N/O contact
signal
BI signal selected by
setting [DPSY01A-NCLSG]
N/C contact
signal
Phase-B signals
BI signal selected by
N/O contact
setting [DPSY01B-NOPSG]
signal
BI signal selected by
N/C contact
setting [DPSY01B-NCLSG]
signal
Phase-C signals
BI signal selected by
N/O contact
setting [DPSY01C-NOPSG]
signal
BI signal selected by
N/C contact
setting [DPSY01C-NCLSG]
signal
[DPSY01-EN]
On
[DPSY01-DEVTYPE]
3-Pole
[DPSY01-OPC]
And
[DPSY01-CLC]
And
Figure 4.2-40 Acquisition of a state signal
†Note: The user should set the actual input-points. See chapter
Binary IO module
‡Note: In Figure 4.2-40 two signals can be issued: "DPSY01_3PH_STATE" and
"DPSY01_F_QLT_SPP". One is used in the select condition logic and operate
condition logic (see Figure 4.2-13 and Figure 4.2-28). Another is used for operation
in the event suppression function. Other signals are also provided:
DPSY01_APH_STATE, DPSY01_BPH_STATE, and DPSY01_CPH_STATE.
Acquisition of a signal corresponding to a phase
Suppose that a state-signal is acquired on the two BI circuits at IO#1 slot. An individual phase
signal can be taken using the N/C and the N/O contacts; thus, the user should set two input-
points (8001001110 and 810101110 in 200B01†) for the settings [DPSY01A-NOPSG] and
[DPSY01A-NCLSG], respectively, as shown in Figure 4.2-41. The user should set the scheme
switch [DPSY01-DEVTYPE] to 1-Pole.
Signal acquisition logic in DPSY01
DPSY01
&
&
Open
&
&
Faulty
&
&
Intermediate
&
Close
&
&
&
.
- 713 -
6F2S1914 (0.49)
Event
Suppression
&
1≥
detector
&
&
&
Technical description:
GRL200 (Soft 033 & 037)
Output ‡
To select and operate
condition logics
"DPSY01_3PH_STATE"
(511001 3102011001)
"DPSY01_ F_QLT_SPP"
(511001 8102011F5F)