Setting
2.28.3
ICD(Function ID: 480001)
Setting items
ICD-EN
ICD-2f
ICD-OC
Data ID
2.28.4
Signal monitoring point
ICD(Function ID: 480001)
Element ID
8000001C20
8100001C21
8200001C22
8300001C23
Range
Unit
1A rating
5A rating
Off / On
- ICD function scheme switch
10 - 50
% Sensitivity of 2f
0.10 -
0.50 -
A Threshold of fundamental current
5.00
25.00
Name
ICD-A
ICD-B
ICD-C
ICD-OR
- 358 -
Contents
Description
ICD relay element operated (phase-A)
ICD relay element operated (phase-B)
ICD relay element operated (phase-C)
ICD relay element operated (3-phases OR)
6F2S1914 (0.49)
Default
Note
1A
5A
Off
15
0.50
2.50
GRL200 (Soft 033 & 037)