other IEDs and GOOSE, is necessary.
Interlock-check formula
4.7.2
Figure 4.7-2 shows a device (Q0) in the feeder bay, if a control action to operate (Q0) is required,
an interlock-check will be necessary. To control the device (Q0), the interlock-check must verify
the status of several devices in the busbar and the bay.
Busbar1-A
Busbar2-A
Q1
Figure 4.7-2 Example of device status and Interlock-check
In accordance with the arrangement of the devices shown in Figure 4.7-2, interlock-check
formulae can be configured from equations (4.7-1) to (4.7-9). The status of respective devices,
(stVal) and interlock operators ("•" and "+") are placed on the right-hand side of the equations;
and the interlock condition (e.g. Q0(Closing)) is placed on the left-hand side of the equations.
The interlock operators are also shown in Table 4.7-2.
where,
Q1B
Q2
Q52
Q0B
Q0
Q53
Q8
Q9
Q69
F52VT
̅̅̅̅ ∙ Q2
̅̅̅̅ ∙ Q15
̅̅̅̅̅ ∙ Q52
Q1 = (Q0
+ ( Q2 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B )
̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q1
̅̅̅̅ ∙ Q25
Q2 = (Q0
+ ( Q1 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B )
̅̅̅̅ ∙ Q52
Q9 = (Q0
̅̅̅̅̅̅̅̅̅ ∙ 63GBE
Q0 ( Closing
) = 63QBE
̅̅̅̅ ∙ Q2
∙ ( ( Q1
∙ Closing Blocking
Q0 ( Opening
̅̅̅̅ ∙ Q69 ∙ F27L(No voltage) ∙ F52VT )
Q8 = ( Q9
Q52 = ( Q9
Q53 = ( Q9
Q69 = Q8
- 825 -
Q15
Q2B
F27L
̅̅̅̅̅ ∙ Q53
̅̅̅̅̅ )
̅̅̅̅̅ ∙ Q53
̅̅̅̅̅ )
̅̅̅̅̅ ∙ Q53
̅̅̅̅̅ ∙ Q8
̅̅̅̅ )
̅̅̅̅̅̅̅̅̅
̅̅̅̅ ∙ Q9
̅̅̅̅ ) + ( ( Q1 + Q2 ) ∙ Q9))
̅̅̅̅̅̅̅̅̅ ∙ 63GBE
̅̅̅̅̅̅̅̅̅
) = 63QBF
̅̅̅̅ ∙ Q1
̅̅̅̅ ∙ Q2
̅̅̅̅ )
̅̅̅̅ ∙ Q1
̅̅̅̅ ∙ Q2
̅̅̅̅ )
6F2S1914 (0.49)
Q25
(4.7-1)
(4.7-2)
(4.7-3)
(4.7-4)
(4.7-5)
(4.7-6)
(4.7-7)
(4.7-8)
(4.7-9)
GRL200 (Soft 033 & 037)