Toshiba GR200 Series Instruction Manual page 665

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Receiving "operate command Off" from the remote end
(ii)
Figure 4.1-21 depicts the reception of the operate command for 'Off ' from the remote-end.
Wait for a command
Select logics
Select command On from remote-end
Select command Off from remote-end
Select command On from front panel
Select command Off from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Mapping required for Input point from communication
Figure 4.1-22 illustrates the operate logic when an "Operate command Off (Remote-Off-
Control)" signal is applied to the SPOS01 logic. The input-point "DEV01_CONTROL_REQ" is
used for the reception of the "Operate command Off (Remote-Off-Control)".
Input
Command "Remote-Off-Control"
510001_7001016D08
DEV01_CONTROL_REQ
ILK† condition ("Off") passed
SPOS01-Off
User Configurable condition
(PLC#3 connection point)
510001 800101EE56
SPOS01IN_TMP_34
User Configurable condition
(PLC#2 connection point)
510001 810101EDDA
SPOS01IN_TMP_42
ASEQ§ function is in progress
ASEQ_MULTI_SEL
Figure 4.1-22 Operate 'Off' from the remote -end in SPOS01
†Note: The ILK function can provide the operation criteria for "Off".
Wait for a next command
On control from remote-end
Off control from remote-end
Signal reception in
IEC61850
On control from front-panel
Off control from front-panel
On control by PLC function
Off control by PLC function
Figure 4.1-21 Outline of operate command 'Off'
Operate logic in SPOS01
SPOS01 function (Function ID: 510001)
Operate Cmd.
with ILK
condition
&
Operation Cmd.
without ILK
condition
[SPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[SPOS01-LGCFEXOT]
Fixedlogic
[SPOS01-PLSM]*
Var
Fix
"SPOS01-EX_CMP
(5A0101_8001011E93)
- 642 -
Operate logic
Failed
"
SPOS01-FEC_OK_CSF"
(510001_8001011E7F)
1≥
1≥
&
&
&
&
6F2S1914 (0.49)
Success
Operation
Signal output
decision
Do nothing
Output
[SPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"SPOS01_FEX_BO" §§
(510001_8101011DD0)
&
Assign to BOs
To PLC
&
logic
To "Wait for a command"
"
SPOS01_EX_FFL
[SPOS01-RST]
(510001_8601011E91)
0
t
1.0s- 100.0s
Operation Failed
††
GRL200 (Soft 033 & 037)
" † †