Signals from user-PLC logic
Closing-control command requiring ILK† and synchro
checks (PLC#1 connection point)
511001 800201EE35
DEV01_CL_SYNC_INTER
Closing-control command requiring synchro check
(PLC#2 connection point)
511001 800201EE34
DEV01_CL_SYNC
From SYNCHK
SYNC01-SLD_VCS
(560001 840B011F58)
Closing-control command requiring ILK† check
(PLC#3 connection point)
511001 800201EE33
DEV01_CL_INTERLOCK
Closing-control command with no check
(PLC#4 connection point)
DEV01_CL_COMMAND
511001 800201EE32
ILK condition ("Closing") passed
DPSY01-Close
Figure 4.2-10 Select 'Closing' using the PLC function in DPSY01
Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-3 and
††
Table 4.2-10.
†Note: The Software interlocking (ILK) function can provide the operation criteria for
"Closing". The ILK function is discussed separately; note that the operation
criteria is defined in the ILK function itself (i.e., the user cannot set the
condition).
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
Note: A timer is provided to determine a failure to operate. The maximum value of the
§§
settings [SYNC01_TLRDIDRLI] or [SYNC01_TDRDI] is used for the decision time.
For more information on settings, see the SYNDIF function.
Output signal to BO
The DPSY01 function, in Figure 4.2-10, can issue a "Select success" signal at the output-point
"DPSY01_OSL_BO_CSF"
Note: The signal "DPSY01_OSL_BO_CSF" is the same signal as that shown in Figure
1
4.2-2.
Select logic in DPSY01
DPSY01 function (Function ID: 511001)
For DIR operation (PLC#1)
Operate command with ILK
condition & synchro-checking
For DIR operation (PLC#2)
Operate command with
synchro-checking
For DIR operation (PLC#3)
Operate command with ILK
condition
For DIR operation (PLC#4)
Operate command without
condition
Select condition‡
.
1
- 679 -
&
1≥
&
&
0
0.1s
Timer§§
0
t
&
0.0 to 5.0 s
6F2S1914 (0.49)
Output
To "Wait for a next
command"
To BO connection
DPSY01_OSL_BO_FLG"
(511001 8602011DC6)
t
Select "Closing"
To "Wait for a command"
0
t
Select "Failed"
0.6s
††
GRL200 (Soft 033 & 037)