Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.20.6
CBF(Function ID: 453001)
Setting items
CBF-EN
OC
OCCBF-EN
OCCBF1
OCCBF2
EF
EFCBF-EN
EFCBF1
EFCBF2
Timer
TCBF1-RE
TCBF1-TP
TCBF2-RE
TCBF2-TP
Output
CBF1-Retrip
CBF1-Trip
CBF2-Retrip
CBF2-Trip
Range
Unit
1A rating
5A rating
Off / On
- CBF protection scheme switch
Off / On
- Current flow is judged by OC relay operation
0.10 -
0.50 -
OCCBF1 relay operating level (Current flow
A
5.00
25.00
judgment)
0.10 -
0.50 -
OCCBF2 relay operating level (Current flow
A
5.00
25.00
judgment)
Off / On
- Current flow is judged by EF relay operation
0.10 -
0.50 -
EFCBF1 relay operating level (Current flow
A
5.00
25.00
judgment)
0.10 -
0.50 -
EFCBF2 relay operating level (Current flow
A
5.00
25.00
judgment)
0.000 - 300.000
s CBF1 retrip timer
0.000 - 300.000
s CBF1 trip timer
0.000 - 300.000
s CBF2 retrip timer
0.000 - 300.000
s CBF2 trip timer
Off / On / On-T
- CBF1 retrip operation mode
Off / On / On-AftRe
- CBF1 trip operation mode
Off / On / On-T
- CBF2 retrip operation mode
Off / On / On-AftRe
- CBF2 trip operation mode
- 298 -
6F2S1914 (0.49)
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
On
1.00
5.00
1.00
5.00
Off
1.00
5.00
1.00
5.00
0.150
0.200
0.150
0.200
On
On
On
On