Toshiba GR200 Series Instruction Manual page 294

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

For DT characteristic
OCN1
For IDMT characteristic
OCN1 PU
From ICD
ICD-OR
OCN1-2PBlk
Block
OCN1-EN
ON
From VTF
VTF_DETECT
OCN1-VTFBLK
From CTF
CTF_DETECT
OCN1-CTFBLK
8000011BB0
800001EBB0 OCN1_BLOCK
8000011BB1
800001EBB1 OCN1_INST_OP
†Note: The presence of 'OCN1' and 'OCN1PU' signals depends on the operation
characteristic defined with setting [OCN1_Timer], as shown in Table 2.17-5.
Table 2.17-5 Signal behaviors of PLC monitoring points 'OCN1' and 'OCN1PU'
PLC monitoring points
OCN1
OCN1PU
1 :
A pick-up signal is generated instantly when the element operates.
2 :
No signal due that the PU element is killed. Use 'OCN1' in place of this.
3 :
A pick-up signal is generated, but delayed with the IDMT characteristic.
4 :
A pick-up signal is generated instantly.
From OCN1 to OCN4 logics
OCN1-OPT-TRIP
OCN2-OPT-TRIP
OCN3-OPT-TRIP
OCN4-OPT-TRIP
OCN1-OPT-ALARM
OCN2-OPT- ALARM
OCN3-OPT- ALARM
OCN4-OPT- ALARM
OCN1-ARC-BLOCK
OCN2- ARC-BLOCK
OCN3- ARC-BLOCK
OCN4- ARC-BLOCK
&
&
&
&
BLOCK
≥1
&
BLOCK
Figure 2.17-6 Scheme logic of OCN1
DT
IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
1
2
OCN1-OPT
OCN2-OPT
OCN3-OPT
OCN4-OPT
Figure 2.17-7 Grouping logic for TRC/Recording
TOCN1
&
t
&
0.00-300.00s
&
&
≥1
&
DT
OCN1_Timer
OCN1-USEFOR
IEC-NI
IEC-VI
OCN1-ARCBLK
IEC-EI
UK-LTI
IEEE-MI
IEEE-VI
IEEE-EI
US-C02
US-C08
ORIGINAL
Setting [OCN1_Type]
- 271 -
6F2S1914 (0.49)
8000011C23
OCN1†
8000011C27
OCN1PU†
8000011B60
0
≥1
OCN1-OPT
&
OCN1-OPT-TRIP
TRIP
&
OCN1-OPT-ALARM
ALARM
&
BLOCK
OCN1-ARC-BLOCK
3
4
To TRC
≥1
OCN-OPT-TRIP
≥1
OCN-OPT-ALARM
≥1
OCN-ARC-BLEFK
To Recording
OCN1-OPT
OCN2-OPT
OCN3-OPT
OCN4OPT
GRL200 (Soft 033 & 037)
To Grouping logic

Advertisement

Table of Contents
loading