Figure 2.20-3 CBF1 logics (continued from Figure 2.20-2)
Figure 2.20-2 illustrates that CBF trip signals (CBF1-RETRIP) will be issued when
OCCBF1 or EFCBF1 element operates continuously until expiration of timer settings [TCBF1-
RE] and [TCBF1-TP]. Setting [TCBF1-RE] is overridden when On-AftRe is set for scheme
switch [CBF1-TRIP]. When On is set for scheme switch [CBF1-TRIP], timer setting [TCBF1-
RE] is bypassed; [TCBF1-TP] is applied for backup CBF trip.
&