Toshiba GR200 Series Instruction Manual page 360

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.25.5
UVS(Function ID: 471101)
Setting items
BLK
UVSBLK-EN
UVSBLK
TUVBLK
UVS1-EN
UVS2-EN
UVS1
UVS1-Timer
DT
UVS1
UVS1-DPR
TUVS1
IDMT
UVS1
UVS1-DPR
UVS1-TMS
TUVS1R
ORG
UVS1
UVS1-DPR
UVS1-TMS
TUVS1R
Output
UVS1-VTFBlk
UVS1-UseFor
UVS2
UVS2-Timer
DT
UVS2
UVS2-DPR
TUVS2
IDMT
UVS2
UVS2-DPR
UVS2-TMS
TUVS2R
ORG
UVS2
UVS2-DPR
UVS2-TMS
TUVS2R
Output
UVS2-VTFBlk
UVS2-UseFor
Test tool(Function ID: 471101)
Item
Function test
UVS-Test
Range
Unit
1A rating
5A rating
Off / On
- Operation canceled when UVSBLK operated
5.0 – 20.0
V Threshold of UVSBLK element
0.00 – 300.00
s UVSBLK operation delay timer
Off / On
- UVS1 protection scheme switch
Off / On
- UVS2 protection scheme switch
DT / IDMT / Original
- UVS1 delay type
5.0 - 130.0
V UVS1 threshold
100 - 120
% UVS1 drop-out/pick-up ratio
0.00 - 300.00
s UVS1 operating delay time (in DT mode)
5.0 - 130.0
V UVS1 threshold
100 - 120
% UVS1 drop-out/pick-up ratio
0.010 - 100.000
- UVS1 time multiplier (in IDMT mode)
0.0 - 300.0
s UVS1 definite time reset delay
5.0 - 130.0
V UVS1 threshold
100 - 120
% UVS1 drop-out/pick-up ratio
0.010 - 100.000
- UVS1 time multiplier (in ORG mode)
0.0 - 300.0
s UVS1 definite time reset delay
Non / Block
- UVS1 operation block by VTF
Trip / Alarm
- UVS1 used for trip or alarm
DT / IDMT / Original
- UVS2 delay type
5.0 - 130.0
V UVS2 threshold
100 - 120
% UVS2 drop-out/pick-up ratio
0.00 - 300.00
s UVS2 operating delay time (in DT mode)
5.0 - 130.0
V UVS2 threshold
100 - 120
% UVS2 drop-out/pick-up ratio
0.010 - 100.000
- UVS2 time multiplier (in IDMT mode)
0.0 - 300.0
s UVS2 definite time reset delay
5.0 - 130.0
V UVS2 threshold
100 - 120
% UVS2 drop-out/pick-up ratio
0.010 - 100.000
- UVS2 time multiplier (in ORG mode)
0.0 - 300.0
s UVS2 definite time reset delay
Non / Block
- UVS2 operation block by VTF
Trip / Alarm
- UVS2 used for trip or alarm
Range
Unit
1A rating
5A rating
Off / On
- Not to execute UVSBLK element
- 337 -
6F2S1914 (0.49)
Contents
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Off
10.0
10.00
Off
Off
DT
60.0
100
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
DT
60.0
100
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
Default
Note
1A
5A
Off